Electrical Bonding Code
680.26 Equipotential Bonding (A) Performance – The equipotential bonding required shall be installed to reduce voltage gradients in the pool area. (5) Metal Fittings – All metal fittings within or attached to the pool structure shall be bonded. Isolated parts that are not over 100mm (4 in.) in any dimension and do not penetrate into the pool structure more than 25mm (1 in.) shall not require bonding. The following shall be grounded:- All electric equipment within 5 feet of the inside walls of the pool shall be grounded
- All electric equipment associated with re-circulating system of the pool.
- All metal parts of the pool structure, including the reinforcing metal of the pool shell, coping stones and deck.
- All forming shells.
- All metal fittings within or attached to the pool structure.
- Metal parts of electric equipment associated with the pool water circulating system.
- Metal conduit, metal piping, and all fixed parts that are within 5 feet of the inside walls of the pool and that are not separated from the pool by a permanent barrier. Art. 680-22.
- These parts shall be connected to a common bonding grid with a solid copper conductor, insulated, covered or bare, not smaller than No. 8. Connection shall be made by pressure connectors or clamps of brass, copper or copper alloy.
- Wet-niche underwater lighting fixtures.
- Dry-niche underwater lighting fixtures.
- All electric equipment within 5 feet of the inside walls of the pool.
- All electric equipment associated with re-circulating system of the pool.
- Junction boxes.
- Transformer enclosures.
- Grounded fault circuit interrupters.